SA100 'R' Switchgear Analyzer Breaker Testing
 
weis

SA100 'R' Switchgear Analyzer Breaker Testing
SA100 'R' Switchgear Analyzer Breaker Testing  

Introduction

Weis is a specialist company with over 20 years of experience in the commissioning, testing & maintenance of switchgear and power network fault monitoring within the Power Utility Industry.

Based on its successful SA100 Switchgear Analyser, Weis has developed a Reduced version (SA100 ’R’) with fewer channels providing a lower cost robust switchgear test set for performance analysis on high, medium and low voltage circuit breakers.

Breaker Test & Analysis software is an essential 32-bit Windows™ database program that provides an easy to use operator interface for configuring & displaying the SA100 ’R’ test results in graphical and text report formats.

BTA software runs on a standard IBM compatible PC with a 32-bit Windows™ operating system. This permits the transportation of test records to a regular office based or portable computer.

The display and printing of a report can be fully customised to include logo’s, in-house styles, text phrases and results format, thus eliminated the need to manually complete a written form in most cases.

Possible test results which can be computed per phase for each breaker operation include:-

  • Peak Coil Current, Current Pulse Length
  • Operate Times (Main / Resistive)
  • Operate Time Spread (Main / Resistive)
  • On Time, Dead Time
  • Datum Velocity, Velocity at Contact Touch
  • Stroke, Contact Length (Main / Resistive)
  • Contact Separation
  • Travel Overshoot, Rebound
  • Mechanism Times (Pre Latch / Latch Period)
  • Fingerprint Comparison on all channels (Grey Zone Checking)

Features

  • ROBUST SWITCHGEAR TEST AND ANALYSIS SYSTEM FOR PORTABLE OR FACTORY USE
  • COMPUTED RESULTS WITH CUSTOM REPORT FORMAT FEATURE, REDUCING TEST TIME
  • CREATE A ELECTRONIC LIBRARY OF BREAKER TEST SETTINGS AND SIGNATURES
  • REVISED CONFIGURATION / RECALCULATION ON PREVIOUS TESTS CAPABILITY
  • SUBSTATION ENVIRONMENT PROVEN WITH A 12.1” HIGH-BRIGHT COLOUR TFT DISPLAY
  • INDENPENDENT CONTROL OF TRIP AND CLOSE AC OR DC COILS
  • 6 ANALOGUE INPUT FOR: 1 x DUAL RANGE (5 / 30A) TRIP AND CLOSE COIL CURRENT , 1 x TRAVEL, 3 x USER CONFIGURABLE
  • 10 DIGITAL INPUTS FOR: TIMING OF UP TO 4 MAIN AND 4 RESISTIVE CONTACTS, 2 x TIMING CONTACTS (24-250V DC or 0V)

Specifications

INPUTS
Analogue: 1 x Independently controlled trip (open) and close coil current inputs.
1 x Resistive (linear or rotary) travel transducer inputs.
3 x User configurable 0 - 10V DC or 0 - 200mV DC inputs, selected via input sockets.
Analogue Accuracy: <0.5% of fullscale.
Digital: 8 x Contact status inputs providing timing of up to 4 main contacts and 4 resistive contacts (dry contacts).
2 x User configurable inputs for contact timing (24 - 250V DC).
Resistive Contact Range: 15 - 10,000 ohms.
Digital Resolution: 100µSec.
Connectors: 4mm safety socket.
OUTPUTS
Coil Operation: Solid state outputs for trip (open) and close.
Coil Peak Current: 5 or 30A selectable via input sockets.
Coil Max. Voltage: 400V peak.
RECORDING
Resolution: 12 bit A/D (1:4096) and 10 kHz sampling rate.
Recording Time: 60 seconds (64Mbytes RAM).
Synchronisation: All inputs sampled simultaneously
Start trigger: Coil current or selectable on any analogue / digital input.
GENERAL SYSTEM

PS2 sockets for external keyboard with built in trackball.

12.1” TFT SVGA (800x600) “High-Bright” colour display (350cd).

3½” 1.44Mbyte floppy disk drive and EIDE hard disk drive.

VGA port for external screen, RS232 communications port, parallel printer port and USB port.

Windows™ Millennium Edition. All standard Windows Centronics or USB printers supported.

Safety keyswitch to enable/disable coil operation.

REAL-TIME CLOCK
Range: Time, date, leap year and day of the year with internal battery backup. 100mS resolution.
PROGRAMMING - SETTABLE PARAMETERS
User strings: Site name, breaker number, breaker type, line name, operator name and 15 user configurable.
Test times: Close, Open, Trip Free, Close-Open, Open Close, Open-Close-Open.
Coil operate times: Initial delay, trip coil “on-time”, close coil “on-time”, delay time between closing and opening, delay time between opening and closing.
Channels:

Analogue - Input name, fullscale value, units. Digital - Input name.

Datum points: Velocity calculation points on travel (speed) curve.
COMPUTED RESULTS
Up to a sequence of 3 operations detailing 3-phase information: 

Peak coil current, operate times and operate time spread (main/resistive), on time, dead time, datum velocity, velocity at contact touch, stroke, contact length (main/resistive), contact separation, travel overshoot and rebound.

OPERATING VOLTAGES
Prime Power: 100 to 350V DC, 88 to 264V AC auto-sensing via IEC power connection. Burden <60 VA.
ENVIRONMENTAL

Operating

Temperature:

-20ºC to +60ºC (-4ºF to +140ºF)
Humidity: 0 to 97% RH non-condensing.
Isolation: 2kV rms for 1 minute (channel to channel, channel to earth).

Surge Withstand

Transient:

To IEC 801-5. 1.2/50mS.

Common Mode: Severity level class 4.

Series Mode: Severity level class 3.

Fast Transient Burst: To IEC 801-4 level 3.
RFI Immunity: To IEC801-3 level 3. 10V/m 26-1000MHz.
Emissions: To EN50081-1: 1992.
MECHANICAL DETAILS
Enclosure: 6U steel enclosure suitable for Euro 19” wide rack mounting or free standing (tabletop).
Ventilation: Fan assisted.
Weight: <9kg.
Optional Carry Case: Reinforced aluminium with wheels on one end, 710mm(W) x 480mm(H) x 370mm(D).
DUE TO CONTINUING DEVELOPMENT AND IMPROVEMENTS WEIS RESERVES THE RIGHT TO CHANGE THIS SPECIFICATION WITHOUT NOTICE

Windows is a trademark for Microsoft Inc.


Delight Supply Co.,Ltd. 128/109 Phayathai Plaza Building 9th Floor, Phayathai Road, Thung-Phayathai, Radthavee, Bangkok 10400, Thailand
Tel: 02-6129435-6 Fax: 02-612-9437 Email: sales@delightsupply.com